PL750/2S

Tank Diameter with/without Insulation (D/Dsp) 40/32" (1000/800 mm)
Tank Height (H) 75.6* (1920 mm)
Net Weight (Dry) 556 lbs (252 kg)
Total Capacity 200 gal (750 l)
Boiler Water Capacity 73 gal (275 l)
DHW Total Capacity/DHW Standby Portion 80/40 gal (300/1500 l)
Solar Indirect Coil Capacity 0.37 gal (1.4 l)
Solar Indirect Coil Length 11 ft² (1.0 m²)
Standby Heat Loss 13,000 BTU/day (3.7kWh/24h)
Continuous Output (Upper Indirect Coil) with 176/113/50°F (80/45/10°C) 96,000 BTU/Hr [182 gph]
(28kW[688 l/hr])
Max. Operating Pressure (Solar Indirect Coil/Boiler Water/DHW) 116/44/145 psi (8/3/10 bar)
Max. Operating Temperature Heating Water/DHW 203°F (95°C)
 
  Pipe Size Height
from Ground
Cold Water Inlet (EK) 1" .31" (8 mm)
Cold Water Drain (EL) 1¼" 8.5 (215 mm)
Solar/DHW Drain (EL1/E2) ¾" 3.9" (100 mm)
Storage Tank Return on the Solar Side (RS1) ¾"  
Storage Tank Supply on the Solar Side (VS1) ¾" 6.7" (170 mm)
Return, Oil/Gas Fired/Condensing Boiler for DHW Heating (RS2) 1¼" 40.7" (1033 mm)
Supply, Oil/Gas Fired/Condensing Boiler for DHW Heating (VS2) 1¼" 65.7" (1668 mm)
Return, Oil/Gas Fired Boiler (RS2) 1¼" 19.7" (550 mm)
Supply, Oil/Gas Fired Boiler (VS5) 1¼" 31" (788 mm)
Return, Boiler Circuits (RS4) 1¼" 14.6" (370 mm)
Supply, Boiler Circuits (VS4) 1¼" 35.9" (911 mm)
Return, Solid Fuel Boiler (RS5) 1¼"  
Supply, Solid Fuel Boiler (VS2) 1¼" 65.7" (1668 mm)
DHW Circulation Inlet (EZ) ¾"  
DHW Outlet (AW) 1¾"  
     