Venting Requirements for the GA124:
Intake: Use 3" galvanized pipe or flexible pipe. See manual for venting details.
Exhaust: Use 3" approved AL29-4C stainless steel venting material (Heat-Fab, Flex-L, Pro-Tech,
Z-Flex) Use condensate drain as starting piece at 3" boiler exhaust connection. One 90° elbow
is equivalent to 10' of equivalent length, 2 45° elbows equivalent to 10' of vent pipe Maintain
minimum 1" clearance to combustibles for vent pipe in unenclosed spaces (Flex-L, Z-Flex) Slope
exhaust system upward from the boiler ¼" per foot. Use high temperature silicone (GE 106 or
equivalent) for sealing of vent component.